Model HTG-1000GF
Prime Power kVA/kW 1250/1000
Rated speed r/min 1000
Engine Model Model 16M33D1280NG10 1104
Bore x Stroke (mm) 150 x 185
Displacement (L) 52.3
N° of Cylinders 16
Cylinders Arrangement At Vee
Fuel System Open Chamber / Lean Burn
Governor (Gov.) ECU
Aspiration (Asp.) Turbocharged & air-to-water cooled
Low emission standard, lean burn technology resulting in lower NOx emissions
High transient and block load capabilities
Full duty cycle capability, from prime to continuous power
Electronically controlled high efficiency engines
Lubrication system
Full flow screwable oil filters
Lube oil purifier with replaceable cartridge
Water cooled lube oil cooler
Continuous Power (COP)
Continuous Power is the maximum power available for an unlimited period of use at a constant load factor. No overload
capability is allowed.
Unlimited Prime Rated Power (PRP)
Prime Power is the maximum power available for unlimited hours of usage in a variable load application. The average load
factor should not exceed 70% of the engine's PRP power rating during any 24 hour period. An overload capability of 10% is
available, however, this is limited to 1 hour within every 12 hour period.
1) All ratings are based on operating conditions under ISO 8528-1, ISO 3046, DIN6271. Performance tolerance of +-5%.
2) Test conditions: 100 kPa, 25 deg.C air inlet temperature, relative humidity of 30%, with fuel density 0.84 kg/L. Derating may
be required for conditions outside these; please contact the factory for details.
3) Power output curves are based on the engine operating with fuel system, water pump and lubricating oil pump; not
included are battery charging alternator, fan and optional equipment.
Starting method 24V Electric
Rated Voltage 400V/230V
Rated Frequency 50Hz/60Hz
Type Open/Silent/Soundproof/Container
Alternator Type Brushless
Brand Stamford, Leroy-Somer, Faraday, Lingyu, etc.
Connection 3-phase, 4-wire
Controller Type Auto PLC Controller
Brand Deepsea, SmartGen, ComAp etc.
Fuel Natural Gas 0.3m3/kw3h
Prime Power (PRP): Prime power is available for an unlimited number of annual hours in variable load application, in
accordance with GB/T2820 -97 (eqv ISO8528);
A 10% overload capability is available for a period of 1 hour within a 12-hour period
of operation.
Standby Power Rating (ESP): The standby power rating is applicable for supplying emergency power for the duration of a utility
power interruption. No overload, utility parallel or negotiated outage operation capability is available at this rating.
Rated Voltage: generally the rated power includes 380/220V, 400/230V, 415/240V, 440/254V, we make it according to client's
requirements.
Control Panel
The DSE7310 is an Auto Start Control Module and the DSE7320 is an Auto
Mains (Utility) Failure Control Module suitable for a wide variety of single.
Attachment (Optional Parts)
40ft Container canopy
Scientific and efficient Special sand-proof waterproof blinds with illumination.
Soundproof Canopy
(Super Silent canopy)Containerized Canopy
CHP system (Exhaust Heat Collector)
1. The unique spiral winding structure increases the turbulence effect, and the heat exchange capacity per unit area is 3-7 times that of the traditional heat exchanger.
2. High heat transfer coefficient, high heat exchanger heat transfer efficiency, good heat transfer effect, high heat transfer coefficient up to 14000W/m·k, energy saving effect is remarkable.
3. Small size. With only one-tenth of the traditional tube and shell heat exchangers, it takes up less space and reduces infrastructure and installation and maintenance costs.
4. Using a small clearance design to increase the flow rate, the heat exchanger is not easy to foul, and the use and maintenance costs
are low.
5. Advanced design concept, the length of the heat exchange tube is 3-4 times the height of the cylinder, the material stays longer and the
heat transfer is more fully.
6. Spiral-wound elastic tube bundle design can effectively eliminate pipe vibration and stress due to thermal expansion and contraction deformation.
7. Unique 90 degree connection, heat exchangers all participate in heat exchange,
no dead ends and stagnant areas, reduce fluid resistance.
8. Counter-current heat transfer, asymmetric flow design, in the vapor-liquid heat transfer field has other advantages that can not be compared with heat exchangers.
Automatic Paralleling and Gridconnect Control System
This system can connect generator sets in parallel or connect the generator set to the grid automatically.
CHP/Cogeneration/CCHP/Trigeneration
Remote Control
PMG Alternator
Oil and Water Heater
High Voltage Alternator 6.3kv and 10.5kv, High Voltage Electrical Control Cells (PT Cabinet
CT Cabinet
High Voltage outgoing cabinet
DC Panel, Groud Resistance Cabinet and low voltage distribution cabinet etc)
Remarks:
Both 50Hz and 60Hz are available.
> Special voltages available.
Alternator brand Stamford,Leroy Somer,Marathon are optional.
Controller brand Deepsea, Comap are optional.
Special requirements for Soundproof Canopy, ATS, Parallel & Synchronization Control, CHP and Biogas Pre-treatment Machinery are optional
The data herein can vary depending on individual production
Sea-Level<1000m , Temp<40